← Security Alerts

CVE-2019-10929

Siemens · published 2019-08-13

Source record Collected from the National Vulnerability Database (NVD)

Description

Description by Siemens AG via the CVE Program.

A vulnerability has been identified in SIMATIC CP 1626 (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V20.8), SIMATIC HMI Panel (incl. SIPLUS variants) (All versions), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.4.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.8.1), SIMATIC S7-1500 Software Controller (All versions < V20.8), SIMATIC S7-PLCSIM Advanced (All versions < V3.0), SIMATIC STEP 7 (TIA Portal) (All versions < V16), SIMATIC WinCC (TIA Portal) (All versions < V16), SIMATIC WinCC OA (All versions < V3.16 P013), SIMATIC WinCC Runtime Advanced (All versions < V16), SIMATIC WinCC Runtime Professional (All versions < V16), TIM 1531 IRC (incl. SIPLUS NET variants) (All versions < V2.1). Affected devices contain a message protection bypass vulnerability due to certain properties in the calculation used for integrity protection. This could allow an attacker in a Man-in-the-Middle position to modify network traffic sent on port 102/tcp to the affected devices.

Status at the source

Affected products, as the source lists them

VendorProductVersions
SiemensSIMATIC CP 1626All versions: affected
SiemensSIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants)All versions: affected
SiemensSIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants)All versions < V20.8: affected
SiemensSIMATIC HMI Panel (incl. SIPLUS variants)All versions: affected
SiemensSIMATIC NET PC Software V14All versions < V14 SP1 Update 14: affected
SiemensSIMATIC NET PC Software V15All versions: affected
SiemensSIMATIC S7-1200 CPU family (incl. SIPLUS variants)All versions < V4.4.0: affected
SiemensSIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)All versions < V2.8.1: affected
SiemensSIMATIC S7-1500 Software ControllerAll versions < V20.8: affected
SiemensSIMATIC S7-PLCSIM AdvancedAll versions < V3.0: affected
SiemensSIMATIC STEP 7 (TIA Portal)All versions < V16: affected
SiemensSIMATIC WinCC (TIA Portal)All versions < V16: affected
SiemensSIMATIC WinCC OAAll versions < V3.16 P013: affected
SiemensSIMATIC WinCC Runtime AdvancedAll versions < V16: affected
SiemensSIMATIC WinCC Runtime ProfessionalAll versions < V16: affected
SiemensTIM 1531 IRC (incl. SIPLUS NET variants)All versions < V2.1: affected
Products named in NVD's CPE match criteria (20)
  • cpe:2.3:o:siemens:simatic_et_200sp_open_controller_cpu_1515sp_pc_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_et_200sp_open_controller_cpu_1515sp_pc2_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_s7-1200_cpu_1211c_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_s7-1200_cpu_1212c_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_s7-1200_cpu_1214c_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_s7-1200_cpu_1215c_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_s7-1200_cpu_1217c_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_s7-1500_cpu_1518_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_s7-1500_cpu_1511c_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_s7-1500_cpu_1512c_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:simatic_net_pc:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:simatic_s7-1500:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:simatic_s7-plcsim_advanced:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:simatic_step_7:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:simatic_wincc:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:simatic_wincc_open_architecture:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:simatic_wincc_runtime:*:*:*:*:advanced:*:*:*
  • cpe:2.3:o:siemens:simatic_cp_1626_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_tim_1531_irc_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_hmi_panel_firmware:*:*:*:*:*:*:*:*

DeSpy has not checked any unit, hardware revision or firmware. A product missing here is not a statement that it is unaffected.

Scores, as their sources published them

DeSpy does not score records. These are the sources' own values.

Weaknesses

CWE-327, NVD-CWE-Other

Sources

References the source lists

Source dates: published 2019-08-13, last changed 2026-06-17. DeSpy's copy of this version is dated 2026-09-28.

This product uses the NVD API but is not endorsed or certified by the NVD.

CVE records: Copyright © 1999-2026, The MITRE Corporation. CVE is a trademark and the CVE logo is a registered trademark of The MITRE Corporation.

CVE Usage: MITRE hereby grants you a perpetual, worldwide, non-exclusive, no-charge, royalty-free, irrevocable copyright license to reproduce, prepare derivative works of, publicly display, publicly perform, sublicense, and distribute Common Vulnerabilities and Exposures (CVE™). Any copy you make for such purposes is authorized provided that you reproduce MITRE's copyright designation and this license in any such copy.

CISA's Known Exploited Vulnerabilities catalog and CISA Vulnrichment data are CC0 1.0. CISA advisories are shown with the TLP label their document carries. No endorsement by CISA, DHS, NIST or MITRE is stated or implied.

Scope, sources and licences →