← Security Alerts

CVE-2019-6575

Siemens · published 2019-04-17

Source record Collected from the National Vulnerability Database (NVD)

Description

Description by Siemens AG via the CVE Program.

A vulnerability has been identified in SIMATIC CP 443-1 OPC UA (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V2.7), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants) (All versions < V15.1 Upd 4), SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants) (All versions < V15.1 Upd 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Upd 4), SIMATIC IPC DiagMonitor (All versions < V5.1.3), SIMATIC NET PC Software V13 (All versions), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC RF188C (All versions < V1.1.0), SIMATIC RF600R family (All versions < V3.2.1), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.5 < V2.6.1), SIMATIC S7-1500 Software Controller (All versions between V2.5 (including) and V2.7 (excluding)), SIMATIC WinCC OA (All versions < V3.15 P018), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Upd 4), SINEC NMS (All versions < V1.0 SP1), SINEMA Server (All versions < V14 SP2), SINUMERIK OPC UA Server (All versions < V2.1), TeleControl Server Basic (All versions < V3.1.1). Specially crafted network packets sent to affected devices on port 4840/tcp could allow an unauthenticated remote attacker to cause a denial of service condition of the OPC communication or crash the device. The security vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the OPC communication.

Status at the source

Affected products, as the source lists them

VendorProductVersions
SiemensSIMATIC CP 443-1 OPC UAAll versions: affected
SiemensSIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants)All versions < V2.7: affected
SiemensSIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants)All versions < V15.1 Upd 4: affected
SiemensSIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants)All versions < V15.1 Upd 4: affected
SiemensSIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900FAll versions < V15.1 Upd 4: affected
SiemensSIMATIC IPC DiagMonitorAll versions < V5.1.3: affected
SiemensSIMATIC NET PC Software V13All versions: affected
SiemensSIMATIC NET PC Software V14All versions < V14 SP1 Update 14: affected
SiemensSIMATIC NET PC Software V15All versions: affected
SiemensSIMATIC RF188CAll versions < V1.1.0: affected
SiemensSIMATIC RF600R familyAll versions < V3.2.1: affected
SiemensSIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)All versions >= V2.5 < V2.6.1: affected
SiemensSIMATIC S7-1500 Software ControllerAll versions between V2.5 (including) and V2.7 (excluding): affected
SiemensSIMATIC WinCC OAAll versions < V3.15 P018: affected
SiemensSIMATIC WinCC Runtime AdvancedAll versions < V15.1 Upd 4: affected
SiemensSINEC NMSAll versions < V1.0 SP1: affected
SiemensSINEMA ServerAll versions < V14 SP2: affected
SiemensSINUMERIK OPC UA ServerAll versions < V2.1: affected
SiemensTeleControl Server BasicAll versions < V3.1.1: affected
Products named in NVD's CPE match criteria (27)
  • cpe:2.3:o:siemens:simatic_cp443-1_opc_ua_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_et_200_open_controller_cpu_1515sp_pc2_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_ipc_diagmonitor_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_net_pc_software_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_rf188c_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_rf600r_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_s7-1500_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:opc_unified_architecture:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:simatic_s7-1500_software_controller:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:simatic_wincc_oa:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:simatic_wincc_runtime_advanced:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:simatic_wincc_runtime_comfort:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:simatic_wincc_runtime_hsp_comfort:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:simatic_wincc_runtime_mobile:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:sinec-nms:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:sinema_server:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:sinumerik_opc_ua_server:*:*:*:*:*:*:*:*
  • cpe:2.3:a:siemens:telecontrol_server_basic:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_s7-1500f_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_s7-1500s_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_s7-1500t_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_hmi_comfort_outdoor_panels_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_hmi_ktp_mobile_panels_ktp400f_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_hmi_ktp_mobile_panels_ktp900_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_hmi_ktp_mobile_panels_ktp700f_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_hmi_ktp_mobile_panels_ktp700_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:siemens:simatic_hmi_ktp_mobile_panels_ktp900f_firmware:*:*:*:*:*:*:*:*

DeSpy has not checked any unit, hardware revision or firmware. A product missing here is not a statement that it is unaffected.

Scores, as their sources published them

DeSpy does not score records. These are the sources' own values.

Weaknesses

CWE-248, CWE-755

Sources

References the source lists

Source dates: published 2019-04-17, last changed 2026-06-17. DeSpy's copy of this version is dated 2026-09-28.

This product uses the NVD API but is not endorsed or certified by the NVD.

CVE records: Copyright © 1999-2026, The MITRE Corporation. CVE is a trademark and the CVE logo is a registered trademark of The MITRE Corporation.

CVE Usage: MITRE hereby grants you a perpetual, worldwide, non-exclusive, no-charge, royalty-free, irrevocable copyright license to reproduce, prepare derivative works of, publicly display, publicly perform, sublicense, and distribute Common Vulnerabilities and Exposures (CVE™). Any copy you make for such purposes is authorized provided that you reproduce MITRE's copyright designation and this license in any such copy.

CISA's Known Exploited Vulnerabilities catalog and CISA Vulnrichment data are CC0 1.0. CISA advisories are shown with the TLP label their document carries. No endorsement by CISA, DHS, NIST or MITRE is stated or implied.

Scope, sources and licences →