ICSA-17-187-03F: ICSA-17-187-03F Siemens SIPROTEC 4 and SIPROTEC Compact (Update F)
CISA advisory · released 2017-07-04
Source record Collected from CISA's CSAF advisory feed
- Distribution label in the document: TLP:WHITE
- Revision 9, 2018-06-12 (final)
Products, as the advisory lists them
| Vendor | Product | Version |
|---|---|---|
| Siemens | Firmware variant PROFINET IO for EN100 Ethernet module | <V1.04.01 |
| Siemens | Firmware variant Modbus TCP for EN100 Ethernet module | <V1.11.00 |
| Siemens | Firmware variant DNP3 TCP for EN100 Ethernet module | <V1.03 |
| Siemens | Firmware variant IEC 104 for EN100 Ethernet module | <V1.21 |
| Siemens | EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 | <1.02.02 |
| Siemens | SIPROTEC 7SJ686 | <V_4.83 |
| Siemens | SIPROTEC 7SJ686 | <V_4.87 |
| Siemens | SIPROTEC 7UT686 | <V_4.01 |
| Siemens | SIPROTEC 7UT686 | <V_4.02 |
| Siemens | SIPROTEC 7SD686 | <V_4.03 |
| Siemens | SIPROTEC 7SD686 | <V_4.05 |
| Siemens | SIPROTEC 7SJ66 | <V_4.20 |
| Siemens | SIPROTEC 7SJ66 | <V_4.30 |
DeSpy has not checked any unit, hardware revision or firmware.
Vulnerabilities in this advisory
- CVE-2015-5374 · CWE-20
Specially crafted packets sent to port 50000/UDP could cause a denial-of-service of the affected device. A manual reboot may be required to recover the service of the device.
- CVE-2016-4784 · CWE-862
The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain sensitive device information if network access was obtained.
- CVE-2016-4785 · CWE-862
The integrated web server (port 80/tcp) of the affected devices could allow remoteattackers to obtain a limited amount of device memory content if network access was obtained. This vulnerability only affects EN100 Ethernet module included in SIPROTEC4 and SIPROTEC Compact devices.
- CVE-2016-7112 · CWE-862
Attackers with network access to the device's web interface (port 80/tcp) could possibly circumvent authentication and perform certain administrative operations.
- CVE-2016-7113 · CWE-20
Specially crafted packets sent to port 80/tcp could cause the affected device to go into defect mode.
- CVE-2016-7114 · CWE-287
Attackers with network access to the device's web interface (port 80/tcp) could possibly circumvent authentication and perform certain administrative operations. A legitimate user must be logged into the web interface for the attack to be successful.
Acknowledgments, as the advisory lists them
- Siemens: reported this vulnerability to CISA.
The advisory's legal notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Sources
DeSpy's copy of this version is dated 2026-09-28.
This product uses the NVD API but is not endorsed or certified by the NVD.
CVE records: Copyright © 1999-2026, The MITRE Corporation. CVE is a trademark and the CVE logo is a registered trademark of The MITRE Corporation.
CVE Usage: MITRE hereby grants you a perpetual, worldwide, non-exclusive, no-charge, royalty-free, irrevocable copyright license to reproduce, prepare derivative works of, publicly display, publicly perform, sublicense, and distribute Common Vulnerabilities and Exposures (CVE™). Any copy you make for such purposes is authorized provided that you reproduce MITRE's copyright designation and this license in any such copy.
CISA's Known Exploited Vulnerabilities catalog and CISA Vulnrichment data are CC0 1.0. CISA advisories are shown with the TLP label their document carries. No endorsement by CISA, DHS, NIST or MITRE is stated or implied.