ICSA-18-317-02: Siemens S7-400 CPUs (Update B)
CISA advisory · released 2018-11-13
Source record Collected from CISA's CSAF advisory feed
- Distribution label in the document: TLP:WHITE
- Revision 6, 2023-05-09 (final)
CISA's summary
Summary: Two vulnerabilities have been identified in the SIMATIC S7-400 CPU family that could allow an attacker to cause a denial of service condition. In order to exploit the vulnerabilities, an attacker must have access to the affected devices on port 102/tcp via Ethernet, PROFIBUS or Multi Point Interfaces (MPI). Siemens has released updates for several affected products and recommends to update to the latest versions. Siemens recommends specific countermeasures for products where updates are not, or not yet available.
Products, as the advisory lists them
| Vendor | Product | Version |
|---|---|---|
| Siemens | SIMATIC S7-400 CPU 412-1 DP V7 (6ES7412-1XJ07-0AB0) | vers:all/* |
| Siemens | SIMATIC S7-400 CPU 412-2 DP V7 (6ES7412-2XK07-0AB0) | vers:all/* |
| Siemens | SIMATIC S7-400 CPU 414-2 DP V7 (6ES7414-2XL07-0AB0) | vers:all/* |
| Siemens | SIMATIC S7-400 CPU 414-3 DP V7 (6ES7414-3XM07-0AB0) | vers:all/* |
| Siemens | SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0) | vers:all/<V7.0.3 |
| Siemens | SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES7414-3FM07-0AB0) | vers:all/<V7.0.3 |
| Siemens | SIMATIC S7-400 CPU 416-2 DP V7 (6ES7416-2XP07-0AB0) | vers:all/* |
| Siemens | SIMATIC S7-400 CPU 416-3 DP V7 (6ES7416-3XS07-0AB0) | vers:all/* |
| Siemens | SIMATIC S7-400 CPU 416-3 PN/DP V7 (6ES7416-3ES07-0AB0) | vers:all/<V7.0.3 |
| Siemens | SIMATIC S7-400 CPU 416F-2 DP V7 (6ES7416-2FP07-0AB0) | vers:all/* |
| Siemens | SIMATIC S7-400 CPU 416F-3 PN/DP V7 (6ES7416-3FS07-0AB0) | vers:all/<V7.0.3 |
| Siemens | SIMATIC S7-400 CPU 417-4 DP V7 (6ES7417-4XT07-0AB0) | vers:all/* |
| Siemens | SIMATIC S7-400 CPU 412-2 PN V7 (6ES7412-2EK07-0AB0) | vers:all/<V7.0.3 |
| Siemens | SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) | vers:all/* |
| Siemens | SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) | vers:all/<V6.0.9 |
| Siemens | SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) | vers:all/* |
| Siemens | SIMATIC S7-410 CPU family (incl. SIPLUS variants) | vers:all/<V8.2.1 |
| Siemens | SIPLUS S7-400 CPU 414-3 PN/DP V7 (6AG1414-3EM07-7AB0) | vers:all/<V7.0.3 |
| Siemens | SIPLUS S7-400 CPU 416-3 PN/DP V7 (6AG1416-3ES07-7AB0) | vers:all/<V7.0.3 |
| Siemens | SIPLUS S7-400 CPU 416-3 V7 (6AG1416-3XS07-7AB0) | vers:all/* |
| Siemens | SIPLUS S7-400 CPU 417-4 V7 (6AG1417-4XT07-7AB0) | vers:all/* |
DeSpy has not checked any unit, hardware revision or firmware.
Vulnerabilities in this advisory
- CVE-2018-16556 — CVE-2018-16556 · CWE-20
Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.
- CVE-2018-16557 — CVE-2018-16557 · CWE-347
Sending of specially crafted packets to port 102/tcp via Ethernet interface via PROFIBUS or Multi Point Interfaces (MPI) could cause a denial of service condition on affected devices. Flashing with a firmware image may be required to recover the CPU. Successful exploitation requires an attacker to have network access to port 102/tcp via Ethernet interface or to be able to send messages via PROFIBUS or Multi Point Interfaces (MPI) to the device. No user interaction is required. If no access protection is configured, no privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.
Acknowledgments, as the advisory lists them
- Siemens ProductCERT: reporting these vulnerabilities to CISA.
The advisory's legal notice
Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter "License Terms"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter "Terms of Use"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.
Sources
DeSpy's copy of this version is dated 2026-09-28.
This product uses the NVD API but is not endorsed or certified by the NVD.
CVE records: Copyright © 1999-2026, The MITRE Corporation. CVE is a trademark and the CVE logo is a registered trademark of The MITRE Corporation.
CVE Usage: MITRE hereby grants you a perpetual, worldwide, non-exclusive, no-charge, royalty-free, irrevocable copyright license to reproduce, prepare derivative works of, publicly display, publicly perform, sublicense, and distribute Common Vulnerabilities and Exposures (CVE™). Any copy you make for such purposes is authorized provided that you reproduce MITRE's copyright designation and this license in any such copy.
CISA's Known Exploited Vulnerabilities catalog and CISA Vulnrichment data are CC0 1.0. CISA advisories are shown with the TLP label their document carries. No endorsement by CISA, DHS, NIST or MITRE is stated or implied.