ICSA-25-135-17: Siemens RUGGEDCOM ROX II
CISA advisory · released 2025-05-13
Source record Collected from CISA's CSAF advisory feed
- Distribution label in the document: TLP:WHITE
- Revision 3, 2025-11-11 (final)
CISA's summary
Summary: The web interface of RUGGEDCOM ROX II devices contain multiple Client-Side Enforcement of Server-Side Security vulnerabilities that could allow an attacker with a legitimate, highly privileged account on the web interface to get privileged code execution in the underlying OS of the affected products. Siemens has released new versions for the affected products and recommends to update to the latest versions.
Products, as the advisory lists them
| Vendor | Product | Version |
|---|---|---|
| Siemens | RUGGEDCOM ROX MX5000 | vers:intdot/<2.16.5 |
| Siemens | RUGGEDCOM ROX MX5000RE | vers:intdot/<2.16.5 |
| Siemens | RUGGEDCOM ROX RX1400 | vers:intdot/<2.16.5 |
| Siemens | RUGGEDCOM ROX RX1500 | vers:intdot/<2.16.5 |
| Siemens | RUGGEDCOM ROX RX1501 | vers:intdot/<2.16.5 |
| Siemens | RUGGEDCOM ROX RX1510 | vers:intdot/<2.16.5 |
| Siemens | RUGGEDCOM ROX RX1511 | vers:intdot/<2.16.5 |
| Siemens | RUGGEDCOM ROX RX1512 | vers:intdot/<2.16.5 |
| Siemens | RUGGEDCOM ROX RX1524 | vers:intdot/<2.16.5 |
| Siemens | RUGGEDCOM ROX RX1536 | vers:intdot/<2.16.5 |
| Siemens | RUGGEDCOM ROX RX5000 | vers:intdot/<2.16.5 |
DeSpy has not checked any unit, hardware revision or firmware.
Vulnerabilities in this advisory
- CVE-2025-32469 — CVE-2025-32469 · CWE-602
The 'ping' tool in the web interface of affected devices is vulnerable to command injection due to missing server side input sanitation. This could allow an authenticated remote attacker to execute arbitrary code with root privileges.
- CVE-2025-33024 — CVE-2025-33024 · CWE-602
The 'tcpdump' tool in the web interface of affected devices is vulnerable to command injection due to missing server side input sanitation. This could allow an authenticated remote attacker to execute arbitrary code with root privileges.
- CVE-2025-33025 — CVE-2025-33025 · CWE-602
The 'traceroute' tool in the web interface of affected devices is vulnerable to command injection due to missing server side input sanitation. This could allow an authenticated remote attacker to execute arbitrary code with root privileges.
- CVE-2025-40591 — CVE-2025-40591 · CWE-602
The 'Log Viewers' tool in the web interface of affected devices is vulnerable to command injection due to missing server side input sanitation. This could allow an authenticated remote attacker to execute the 'tail' command with root privileges and disclose contents of all files in the filesystem.
Acknowledgments, as the advisory lists them
- Siemens ProductCERT: reporting these vulnerabilities to CISA.
- Trae Mazza, RMC Global: reporting these vulnerabilities to Siemens.
The advisory's legal notice
The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.
Sources
DeSpy's copy of this version is dated 2026-09-28.
This product uses the NVD API but is not endorsed or certified by the NVD.
CVE records: Copyright © 1999-2026, The MITRE Corporation. CVE is a trademark and the CVE logo is a registered trademark of The MITRE Corporation.
CVE Usage: MITRE hereby grants you a perpetual, worldwide, non-exclusive, no-charge, royalty-free, irrevocable copyright license to reproduce, prepare derivative works of, publicly display, publicly perform, sublicense, and distribute Common Vulnerabilities and Exposures (CVE™). Any copy you make for such purposes is authorized provided that you reproduce MITRE's copyright designation and this license in any such copy.
CISA's Known Exploited Vulnerabilities catalog and CISA Vulnrichment data are CC0 1.0. CISA advisories are shown with the TLP label their document carries. No endorsement by CISA, DHS, NIST or MITRE is stated or implied.